SB15-25-IS-xx-12
26
L
Werkseinstellungen dieses Wechselrichters | Default settings of this inverter | Εργοστασιακές ρυθμίσεις
αυτού του μετατροπέα | Ajustes de fábrica de este inversor | Réglages par défaut de cet onduleur |
Impostazioni di fabbrica di questo inverter | Výrobní nastavení tohoto střídače | Fabrieksinstellingen van
deze omvormer | Nastawy fabryczne falownika | Configurações de fábrica deste inversor
Country Setting: Default
Voltage and frequency monitoring
Threshold
Max. disconnection time
Lower limit AC voltage
195.5 V
0.2000 s
Upper limit AC voltage
264.5 V
0.2000 s
Lower limit AC frequency
47.50 Hz
0.2000 s
Upper limit AC frequency
51.50 Hz
0.2000 s
Loss of mains
active
Max. disconnection time
Active islanding detection
No
-- s
Time before reconnection
active
Grid monitoring time
Time to reconnection after a grid failure
No
-- s
Grid quality
active
Threshold
DC injection - max allowed value for the
offset of the AC current
No
-- A
Voltage rise protection - monitoring of
10 min. mean value, e.g. as per
EN 50160
Yes
253.0 V
K
Wechselrichter über Ethernet konfigurieren | Configuring the inverter via Ethernet | Διαμόρφωση μετατροπέa
μέσω Ethernet | Configuración del inversor mediante ethernet | Configuration de l’onduleur via Ethernet |
Configurazione dell‘inverter mediante Ethernet | Konfigurace střídačů prostřednictvím Ethernetu | Omvormers
via ethernet configureren | Konfiguracja falownika poprzez Ethernet | Configurar inversores via Ethernet
1
Sunny Boy 2.5
Login
Language
User group
Password
Forgot your password?
English
Login
File
Edit
View
Favorites
Tools
Help
169.254.100.1
2