Mapa pics – CIRCUTOR CVM-C10 Series Instrukcja Obsługi
Strona 75
4.10.5. MAPA PICS
PICS
Vendor Name:
CIRCUTOR
Product Name:
CVM-C10
Product Model Number:
0116
Application Software Version:
1.0
Firmware Revision:
0.7.1
BACnet Protocol Revision: 10
Product Description:
Electrical energy meter
BACnet Standardized Device Profile (Annex L)
x
BACnet Application Specific Controller (B-ASC)
List all BACnet Interoperability Building supported (see Annex K in BACnet Addendum 135d):
DS-RP-B Read Property
DS-WP-B Write Propery
DS-RPM-B Read Property Multiple
DM-DDB-B Dynamic Device Binding
DM-DOB-B Dynamic Object Binding
DM-DCC-B Device Communication Control
DM-RD-B Reinitialize Device
Which of the following device binding methods does the product support? (check one or more)
x
Recive Who-Is, send I-Am (BIBB DM-DDB-B)
x
Recive Who-Has, send I-Have (BIBB DM-DOB-B)
Standard Object Types Supported:
Analog Input Object Type
1. Dynamically creatable using BACnet’s CreateObject service?
No
2. Dynamically deleatable using BACnet’s DeleteObject service?
No
3. List of optional properties supported:
max_pres_value
min_pres_value
4. Listo f all properties that are writable where not otherwisa required by this standard
5. List of proprietary properties:
6. List of any property value range restrictions:
Properly Identifier
Object_Name
max 32 characters
DESCRIPTION
SYMBOL ID OBJECTS OBJECT NAME UNITS
Napięcie faza-neutralny
Voltage phase to
neutral
V 1
AI0
Ph2NU1
V
Prąd
Current
A 1
AI1
Ph1Current
A
Moc czynna
Active power
kW 1
AI2
ActPwrPh1
kW
Moc bierna
Reactive power
kvar 1
AI3
ReactPwrPh1
kvar
Współczynnik mocy
Power factor
PF 1
AI4
PwrFactPh1
PF
Napięcie faza-neutralny
Voltage phase to
neutral
V 2
AI5
Ph2NU2
V
Prąd
Current
A 2
AI6
Ph2Current
A
Moc czynna
Active power
kW 2
AI7
ActPwrPh2
kW
Moc bierna
Reactive power
kvar 2
AI8
ReactPwrPh2
kvar
Współczynnik mocy
Power factor
PF 2
AI9
PwrFactPh2
PF
75
Instrukcja obsługi
CVM-C10